Seprol S2000 Nano

Battery operated, ultra-low power wireless telemetry unit and data logger for remote applications

Seprol S2000 Nano

IP68-rated rugged construction, exceptional battery life and compact footprint

Cost Effective | Rugged | Battery Powered | Secure

The IP68-rated rugged construction, exceptional battery life and compact footprint mean the Seprol S2000 Nano remote telemetry unit is ideal for demanding applications in the harshest and most remote environments.
Features & Benefits At A Glance
Ovarro_Icons_F&B_NoTitles_Colour_RGB_Tech Spec.svg

IP68 Rugged, compact design

Ovarro_Icons_F&B_NoTitles_Colour_RGB_Time-Saving.svg

Speedier issue diagnosis

Ovarro_Icons_F&B_NoTitles_Colour_RGB_Battery.svg

High-power lithium battery

Ovarro_Icons_F&B_NoTitles_Colour_RGB_Global.svg

Access asset data from any web browser

WITS Certified

The S2000 is a fully WITS (Water Industry Telemetry Standards) compliant device proving its interoperability with other WITS-approved master stations and field devices.

WITS certified logo
Seprol S2000 Nano IP68 rated RTU
Rugged design

The robust design, combined with a wide operating temperature range of -40C to +70C, a range of mounting options and IP68-rated, rugged, submersible casing means that the S2000 Nano can be used to monitor and control assets in the harshest environments.

Inputs and Outputs

Removable I/O

Yes

Maximum I/O points

1 x Digital Output, 5 x Digital Input, 2 x Analogue Input

Analogue Inputs

Type of input

1 x 0 - 20mA

(not independent)

1 x 0 - 20mA or 0 - 5V

Resolution

20 bits

Accuracy

0.1% (voltage), 0.29% (current)

Sensor supply output

24V DC

Sampling Period

1 second to 1 day

Digital Inputs

Type of input

Volt free contacts

Contact wetting voltage

5V DC nominal

Sampling Period

1ms to 1 day

Digital Outputs

Type of Output

Solid state relay (Photo MOSFET)

Maximum Switching Voltage

16 Vac/35Vdc

Maximum Switching Current

200mAdc

On Resistance (Typical)

10 Ohms

On Resistance (Maximum)

10 Ohms

Processor Unit

Type

Kinetis K66 (ARM Cortex M4)

Flash

8MB Flash + 2 x 1MB CPU Flash

SRAM

RAM 4MB SRAM + 512KB FRAM +, 256KB CPU SRAM

SRAM

RAM 4MB SRAM + 512KB FRAM +, 256KB CPU SRAM

Memory (SD Card)

Up to 32GB

Real-time clock

Yes

Event logging

WITS Log - 32,638 entries (FRAM Log) OR 114,684 entries (SRAM Log) (4MB SRAM), @32,764 Dataset events (WITS) or @76,450 standard DNP point events (4MB SRAM)

Communications

Wireless

GPRS 2G / LTE 4G or GPRS 2G / LTE CAT-M1

Local

USB

Protocols

WITS DNP3 1.1, 1.2, 1.3, Web Server (HTTP), FTP, Telnet, DNP3 Slave

Configuration

Local (PC/Laptop)

YES

Remote via network

YES via WITS DNP3

Programming Languages

Isagraf IEC61131-3 Sequential Function Chart, Function Block, Ladder, Structured Text

Power

Battery (default)

21.6V DC lithium battery 13 Ah

Power down modes

Full Sleep, Snooze with IO monitoring

Environmental

Working temperature

-20°C to +70°C

Storage temperature

-20°C to +85°C

Submersion

IP68 to 4M for 4 days

Dimensions

Width

142mm (5.59”)

Height

197mm (7.75”)

Depth

115mm (4.52”)

Weight

1.5kg

Mounting

Mounting Options

Pole, wall, with wire hanger for metering

Diagnostics

Local watchdog timer

Yes

Communication status

Web page

Configuration display

Web page

I/O Status

Web page

Debug

Web page

Communications analyser

Web page

Certifications

EN 55016-2-3:2006

Radiated emissions (Limits as defined in EN61000-6-3-2007)

EN 61000-4-2:2009

Electrostatic Discharge Immunity Test.

EN 61000-4-3:2006 + A1+A2

Radiated Radio frequency, electromagnetic field Immunity Test.

EN 61000-4-4:2004

Electrical Fast Transient / Burst Immunity Test.

EN 61000-4-6:2009

Immunity to Conducted Disturbances, induced by Radio-frequency Fields

BS EN 60950-1: 2006 + A2:2013

Safety requirements for information technology equipment

IEC 60950-1: 2005 + A2:2013

Safety requirements for information technology equipment

BS EN 61010-1: 2010

Safety requirements for electrical equipment for measurement, control, and laboratory use Part1: General

IEC 61010-1: 2010

Safety Requirements for Electrical Equipment for measurement, control, and laboratory use Part1: General
Seprol Nano Specification Sheet

Locate Your Distributor

Click below to search for your local distributor

Make an enquiry

Need more information? Don't hesitate to get in touch